UPSide — UPS monitoring for Cockpit, powered by NUT

UPSide

UPS monitoring for Cockpit, powered by NUT (Network UPS Tools).

UPSide is a Cockpit plugin that surfaces the state of one or more UPS devices managed by NUT — battery charge and runtime, line/load status, input/output voltage, and the other variables exposed by upsd — directly in the Cockpit web console.

Status: built on the official cockpit-project/starter-kit (React + PatternFly + esbuild). Monitoring is complete; control spans instant commands (upscmd), writable variables (upsrw), and clean shutdown on low battery (upsmon).

How it works

The plugin is a client of a running NUT setup. It uses Cockpit's cockpit.spawn() channel API to call upsc — enumerating UPSes with upsc -l, then reading each one's variables with upsc <name> — and renders them with PatternFly. It does not drive the UPS hardware directly, and it runs no backend service of its own: NUT's upsd is the backend.

A working NUT installation with upsd running and at least one UPS in ups.conf is the prerequisite. By default UPSide reads the local upsd; set a remote source (nutHost — see below) and it reads upsd on another host instead, so you can run UPSide on a secondary that has no UPS of its own (only nut-client is needed there, not nut-server).

Multiple UPSes

UPSide is multi-UPS from the ground up. NUT addresses devices as name (or name@host), so the data layer is modelled as a list of devices:

  • an Overview page shows a card per UPS (status badge, battery %, runtime, load) — the all-at-a-glance view;
  • a Detail view drills into a single UPS (battery gauge, voltages, load, full variable table), with a UPS selector to switch between devices.

A single-UPS install simply shows one card and one detail view.

Requirements

  • Cockpit
  • NUT (upsd running, at least one UPS configured in ups.conf)

Installation

Install on the host that runs Cockpit and NUT.

Runtime: a host running Cockpit, and NUT (nut-server + nut-client) with upsd running and at least one UPS in ups.conf.

Ubuntu / Debian (PPA)

sudo add-apt-repository ppa:deviationist/cockpit-upside
sudo apt update
sudo apt install cockpit-upside

Then reload Cockpit → UPSide appears under System. (Maintainers: the release process for the PPA is in docs/releasing-ppa.md.)

Build & install from source

Requires Node.js ≥ 18 and npm.

git clone https://github.com/deviationist/cockpit-upside.git
cd cockpit-upside
make                 # fetches Cockpit's pkg/lib, installs deps, builds dist/
sudo make install    # → /usr/local/share/cockpit/upside

Install under /usr (where distro packages go) instead of /usr/local:

sudo make install PREFIX=/usr

Reload Cockpit (or log out/in) → UPSide appears under System.

Per-user (no root, for trying it out)

make devel-install     # symlinks ~/.local/share/cockpit/upside → dist/
make devel-uninstall   # remove it

Uninstall

sudo rm -rf /usr/local/share/cockpit/upside   # or $PREFIX/share/cockpit/upside

Historical trends (optional)

Live monitoring works out of the box. For the Trends charts, do the one-time PCP setup in docs/enabling-history.md.

Development

npm install        # install build/runtime deps
npm run watch      # rebuild dist/ on change (esbuild)

Symlink the build into your user's Cockpit path once, then just npm run watch:

make devel-install   # ~/.local/share/cockpit/upside → dist/

Then open Cockpit and find UPSide in the sidebar (reload after rebuilds). See CONTRIBUTING.md for the full setup, conventions, and how to run the tests.

Lint:

npm run eslint
npm run stylelint

Features

  • Monitor / control mode — UPSide is read-only (monitor) by default; control mode surfaces the UPS's instant commands grouped by risk: one-click safe actions (battery self-test, beeper), a confirm step for disruptive-but-recoverable ones (calibrate, bypass), and a collapsed danger zone — load on/off, shutdown sequences — each behind an explicit "this cuts power" acknowledgment (.delay commands take a seconds value). Actions authenticate to NUT with a least-privilege control user (upscmd); the wizard's control step creates or reuses that user (validated by a no-op LOGIN, password entered by you, never read from upsd.users). The file (/etc/cockpit/upside.json) pins the mode when set; otherwise it's a per-browser toggle in Settings.
  • UPS configuration (upsrw) — a per-UPS Configuration view (its own route, from the detail page) lists the UPS's writable variables (low-battery threshold, start/shutdown delays, transfer voltages, …) with type-appropriate editors (number / dropdown / text, validated). Edit several and apply them all at once; read-only in monitor mode, editing is control-mode + authenticated. Setting a variable needs NUT's actions = SET grant — UPSide adds it to the control user on demand if missing.
  • Clean shutdown on low battery (upsmon) — the setup wizard's Shutdown step (and a per-UPS Shutdown settings view) configure upsmon to power the host down before the battery dies: it writes upsmon.conf + the least-privilege monitor login and arms nut-monitor behind an explicit acknowledgment. An opt-in killpower toggle cuts the UPS outlet after shutdown so the host auto-reboots when mains returns — if its BIOS is set to power on after AC loss (firmware UPSide can't change, so it's surfaced as guidance).
  • Event notifications (upsmon) — a per-UPS Notifications view emails on power events (on/low battery, back online, comms lost/restored, …) through a pluggable adapter: a host-side dispatcher runs every script in a drop-in upside-notify.d/ dir, so new backends (webhook, ntfy, MQTT…) are just a script away; the shipped one mails via the system mailer (sendmail/msmtp). Recipient is validated and read-not-sourced, with a Send test to confirm delivery.
  • Guided setup wizard — a PatternFly wizard on its own route (#/setup-wizard); until a UPS is configured the whole app locks to it (no menu, no other pages). Step 1 picks this machine's rolestandalone (UPS here, this box only), netserver (UPS here, shared to other hosts), or netclient (no local UPS — watch one on another host) — and the later steps follow the choice, applying each fix with one click (preview + .bak backup + admin prompt, or the equivalent command), gated behind administrative access:
    • local UPS: install → device (auto-detect with nut-scanner, one-click Install libusb & scan, add a USB HID UPS manually with a preview, a "can't find your UPS?" lsusb troubleshooter) → start & verify;
    • netserver also wires serving: bind upsd to a chosen address (upsd.conf LISTEN), create a secondary login user, and show the firewall command (guidance — UPSide doesn't touch the firewall);
    • netclient: point UPSide at a primary's upsd (sets the remote source);
    • then an optional control step. Scope is connectivity-only — it doesn't configure upsmon shutdown sequencing (that stays the operator's job).
  • Remote NUT source — set "nutHost": "host[:port]" (or pick another host in the wizard) to read/control a upsd over the network — running UPSide on a secondary pointed at the primary. Reads need no credentials; control authenticates a user that exists on the primary. A secondary can also plot the primary's history — see Remote history below.
  • Remote history — a secondary has no local PCP archive, but it can read the primary's history over the network from the primary's PCP pmproxy time-series REST API. Set a Remote history URL in Settings (historyUrl, e.g. https://pcp.example or http://host:44322), with optional HTTP Basic credentials (stored per-browser, like the control creds) — and Trends/Metrics plot the remote UPS just like a local one. It reuses pmproxy (the same series store Cockpit's own metrics use); nothing is stored on the secondary.
  • Overview — a card per UPS (status badge, battery, runtime, load), capability-driven (only shows what the device reports).
  • Detail view per UPS — battery/load donut gauges, runtime, the full NUT variable table, and derived values (battery age, estimated running cost, time-on-battery). A UPS switcher in the breadcrumb.
  • Friendly names — shows the NUT desc from ups.conf, or a custom name you set in the UI, falling back to make/model, with the technical NUT name alongside.
  • Live updates via cockpit.spawn(upsc) polling (NUT has no push model).
  • Historical trends from PCP — a small OpenMetrics scraper feeds NUT into PCP (pmlogger archives it), read back locally with pmrep across multiple daily archive volumes, or remotely from a primary's pmproxy series REST API (see Remote history). Charted on the detail page and a dedicated Metrics page: a two-tier time axis (time/date tick labels plus a day/month/year context band, locale-aware), ranges from 5 minutes to 1 year, a Go to now, hover crosshair, drag-to-zoom, a remembered window, CSV export, configurable retention + an optional dedicated NUT-only archive — and gaps are drawn as gaps (no line bridged across missing data). No embedded database; no NUT PMDA needed.
  • Navigation status — a status icon next to UPSide in the Cockpit menu when a UPS needs attention (via page_status), opt-in.
  • Settings — monitor/control mode, feature toggles, electricity rate/currency, and custom UPS names. File-backed config lives in /etc/cockpit/upside.json (admin-writable, defensively validated on read); the mode falls back to a per-browser preference when the file doesn't pin it.

Roadmap

UPSide is monitoring-complete and now has broad, risk-gated control plus UPS configuration. Done so far:

  • Control actions, all tiers: one-click safe (battery self-test, beeper), confirm-first (calibrate, bypass), and a gated danger zone (load on/off, shutdown) — upscmd, capability-driven per device
  • UPS configuration via upsrw — typed editors, batch apply, actions=SET granted to the control user on demand
  • Setup wizard rebuilt around NUT MODE — standalone / netserver (LISTEN + secondary login + firewall guidance) / netclient roles; locks the app until a UPS is configured
  • Remote upsd support (name@host) — monitor/control a UPS on another host
  • History spanning multiple pmlogger archive volumes
  • Create/reuse of the least-privilege NUT control user
  • Event notifications on power events (upsmon NOTIFY) via a pluggable drop-in adapter (system-mailer default)
  • One-click "enable history" — the wizard installs the PCP scraper + log rule
  • History on a secondary — read the primary's history over its pmproxy series REST API (historyUrl); no local archive or extra storage needed

Future plans:

  • Secondary onboarding (packaging) — a .deb without nut-server so a remote-source host installs lean. (Reading/controlling a remote upsd, the netclient wizard role, and remote history already work; this is packaging polish.)
  • upsmon shutdown sequencing in the wizard — shutdown config exists as its own step/view; folding it into the netserver/netclient role flow would complete that story.

See ROADMAP.md for the full control ladder (tiers A–D) and the principles — capability-driven, least-privilege, no stored secrets — that gate it.

Enabling history: the Trends charts need a one-time host setup (an OpenMetrics scraper + a pmlogger rule that feed NUT into PCP). See docs/enabling-history.md. Live monitoring works without it.

Contributing

Contributions are welcome! See CONTRIBUTING.md and our Code of Conduct. Bug reports and feature requests via GitHub Issues.

License

LGPL-2.1-or-later, matching Cockpit and the starter kit it is based on.